Connor School – Addendum 1
Bid set compared with Addendum
Coverage
Coverage: 9 of 10 structural sheets of this issue compared, 1 stated not compared, 0 silently skipped; earlier issue: 8 compared, 0 stated (0 not reissued), 0 silently skippedChanged on the drawings, not in the narrative (149)
| Change | Old to new | |
|---|---|---|
| Sheet S001 38 changes | ||
| g1 | added CONCRETE NOT EXPOSED TO FREEZING AND THAWING SHAL BE AS FOLLOWS: | |
| g2 | added CONCRETE EXPOSED TO FREEZING AND THAWING SHAL BE AS FOLLOWS: | |
| g3 | note (12 text items) added 5000 PSI @28 DAYS added MINIMUM COMPRESSIVE STRENGTH: added ASTM C150 TYPE II added CEMENT added ASTM C33 OR C330 added AGGREGATE added 1 1/2 INCH added MAXIMUM AGGREGATE SIZE added 0.40 added MAXIMUM WATER-CEMENT RATIO: added 2 TO 4 INCHES added SLUMP: | |
| g4 | note (2 text items) added ASTM C494 added WATER REDUCING ADMIXTURE: | |
| g5 | note (3 text items) added ADMIXTURES SHALL BE USED IN ACCORDANCE WITH ACI AND THE added MANUFACTURERS RECOMMENDATIONS. added USE OF CALCIUM CHLORIDE, CHLORIDE IONS OR OTHER SALTS IS NOT PERMITTED. | |
| g6 | ||
| g7 | ||
| g9 | ||
| g10 | ||
| g11 | added 11. FOOTING AND GRADE BEAM SIZES SHOWN ARE FOR FOOTINGS CONSTRUCTED WITH SIDE | |
| g12 | added 12. SHOP DRAWINGS FOR PLACEMENT SHALL BE SUBMITTED FOR REVIEW PRIOR TO REBAR | |
| g13 | added 13. ALL INSIDE CONCRETE WEARING SURFACES SHALL RECEIVE A SMOOTH STEEL TROWEL FINISH. | |
| g14 | ||
| g15 | ||
| g17 | note (4 text items) added ROOF PANELS SHALL BE APA RATED, EXPOSURE 1, 5/8" (AS NOTED ON DRAWINGS), 5 PLY added PLYWOOD OR HUBER ADVANTECH SHEATHING WITH A MIN. 40/20 SPAN RATING UNLESS added NOTED OTHERWISE ON THE DRAWINGS. SHEATHING SHALL BE EXTERIOR GRADE WHERE added EITHER SIDE OF SHEATHING IS PERMANENTLY EXPOSED TO WEATHER. | |
| g18 | ||
| g19 | ||
| g20 | ||
| g21 | note (4 text items) added WALL PANELS SHALL BE APA RATED, EXPOSURE 1, 1/2"" (AS NOTED ON DRAWINGS), 5 PLY added PLYWOOD OR HUBER ADVANTECH WITH A MIN. 32/16 SPAN RATING UNLESS NOTED added OTHERWISE ON THE DRAWINGS. SHEATHING SHALL BE EXTERIOR GRADE WHERE EITHER added SIDE OF SHEATHING IS PERMANENTLY EXPOSED TO WEATHER. | |
| g22 | ||
| g23 | note (2 text items) added EXTERIOR WALL PANELS SHALL BE ZIP R-6 SHEATHING w/ 0.131"x3" NAILS @4" O.C. EDGE AND added 12" O.C. FIELD. | |
| g24 | ||
| g25 | note (3 text items) added ALL FLOOR AND ROOF SHEATHING SHALL BE INSTALLED WITH THE FACE GRAIN added PERPENDICULAR TO THE SUPPORTS AND A 1/8" GAP AT ALL PANEL EDGES UNLESS added RECOMMENDED OTHERWISE BY THE PANEL MANUFACTURER. | |
| g26 | ||
| g27 | ||
| g28 | note (2 text items) added ALL SHEATHING PANELS SHALL BE INSTALLED WITH END JOINTS STAGGERED UNLESS added NOTED OTHERWISE ON THE DRAWINGS | |
| g29 | added 23. PLACE CONCRETE PER ACI 304. USE INTERNAL MECHANICAL VIBRATION FOR ALL CONCRETE. | |
| g30 | note (2 text items) added WHERE BLOCKING IS NOT SPECIFICALLY REQUIRED FOR THE ROOF SHEATHING, PLY CLIPS added OR TONGUE AND GROOVE PLYWOOD SHALL BE USED. | |
| g31 | note (3 text items) added SUB-FLOOR SHEATHING SHALL BE UNBLOCKED UNLESS NOTED OTHERWISE ON THE added STRUCTURAL DRAWINGS. SUB-FLOOR SHEATHING SHALL BE GLUED DOWN TO THE added SUPPORTING MEMBERS AND GLUED AT THE TONGUE AND GROOVE JOINTS. | |
| g32 | added 24. FIELD TESTING AND INSPECTION OF ALL CONCRETE MATERIALS AND CONCRETE INSTALLATION | |
| g33 | note (5 text items) added ALL NAILS SHALL BE COMMON NAILS. ROOF SHEATHING SHALL UTILIZE RING SHANK NAILS. added STAINLESS STEEL (TYPE 316) NAILS SHALL BE USED AT PERMANENTLY EXPOSED EXTERIOR added AREAS. ALL NAILS THAT ARE NOT EXPOSED TO THE ELEMENTS BUT IN CONTACT WITH added PRESERVATIVE TREATED LUMBER SHALL BE MINIMUM HOT-DIPPED GALVANIZED MEETING added ASTM A153. | |
| g34 | removed | |
| g35 | removed | |
| g37 | removed | |
| g38 | removed | |
| g39 | removed | |
| g40 | graphic: linework drawn differently (no text); 36 px added, 116 px removed at 1.5 px/pt: see the overlay | LOW: check |
| g41 | graphic: linework drawn differently (no text); 99 px added, 1 px removed at 1.5 px/pt: see the overlay | LOW: check |
| Sheet S101 7 changes | ||
| g42 | new detail 1 'FOUNDATION PLAN' (41 text items) added S302 added S303 added BEARING added BEARING added BEARING added BEARING added WALL added WALL added WALL added WALL added 2x6 @16" O.C. added S101 SCALE: 1/4" = 1'-0" added 1' - 3" added 1' - 3" added 1' - 3" added SAW CUT (E) added FOUNDATION STEM added DOWN TO FF added ELEVATION AT (N) added OPENING IN WALL added (E) 6" CMU added (E) 6" CMU added (E) 6" CMU added 17' - 4" added 8" added 1' - 10" added 10' - 8" added T.O.W. = 0' - 8" added T.O.W. = 0' - 8" added T.O.W. = -0' - 10" added T.O.W. = -0' - 10" added STEP T.O. added 6 3/4" added FOUNDATION WALL added 7" added TO AVOID (E) BRICK added VENEER added HSS4X4X5/16 added 12' - 0" added FOUNDATION PLAN added 5' - 7 1/2" | |
| g45 | detail 2 'SLAB AND FRAMING PLAN' removed removed removed | |
| g46 | detail 2 'SLAB AND FRAMING PLAN' removed removed removed | |
| g47 | detail 2 'SLAB AND FRAMING PLAN' removed | |
| g49 | detail 2 'SLAB AND FRAMING PLAN' removed | |
| g50 | detail 2 'SLAB AND FRAMING PLAN' removed | |
| g44 | detail 2 'SLAB AND FRAMING PLAN' removed removed removed | LOW: check |
| Sheet S102 10 changes | ||
| g51 | detail 1 'ROOF FRAMING PLAN' added 5¼"x5¼" PSL added POST DOWN removed removed | |
| g52 | detail 1 'ROOF FRAMING PLAN' added (N) W8x31 removed | |
| g53 | detail 1 'ROOF FRAMING PLAN' removed removed | |
| g54 | detail 1 'ROOF FRAMING PLAN' added (2) 2x6 JACK STUDS AND added (2)2x6 KING STUDS | |
| g55 | detail 1 'ROOF FRAMING PLAN' added (2) 2x6 JACK STUDS | |
| g56 | detail 1 'ROOF FRAMING PLAN' added (2) 1 3/4"x9 1/4" LVL HEADER | |
| g57 | detail 1 'ROOF FRAMING PLAN' | |
| g58 | detail 1 'ROOF FRAMING PLAN' | |
| g59 | added S102 | |
| g60 | detail 1 'ROOF FRAMING PLAN' removed removed removed | |
| Sheet S200 1 change | ||
| g61 | detail 1 'STRUCTURAL FRONT ELEVATION' removed removed removed removed | LOW: check |
| Sheet S300 15 changes | ||
| g65 | new detail 'TYPICAL INTERIOR SLAB DETAIL' (12 text items, 3 graphic areas) added SCALE: 3/4" = 1'-0" added 10 MIL VAPOR BARRIER, added TYP added 6" MINIMUM added COMPACTED added STRUCTURAL BACKFILL added 5" added (MIN.) added T/4 CLEAR removed graphic: lines of the earlier issue no longer drawn (no text); 0 px added, 2819 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 6027 px added, 10703 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 149 px added, 353 px removed at 1.5 px/pt: see the overlay | |
| g66 | new detail 'CONTROL JOINT AT INTERIOR SLAB' (14 text items, 2 graphic areas) added SCALE: 3/4" = 1'-0" added SLAB REINFORCEMENT, added 1 1/4" DEEP SAWCUT OR added TYPICAL added FORMED JOINT w/ added SEALANT added CUT EVERY OTHER added REINFORCEMENT AT added CONTROL JOINT added 1 1/2" added 1 1/2" added CONTROL JOINT AT INTERIOR SLAB removed removed graphic: linework drawn differently (no text); 6332 px added, 10870 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 130 px added, 70 px removed at 1.5 px/pt: see the overlay | |
| g67 | detail 1 'STRUCTURAL SECTION 1' added WOOD HEADER added SEE PLAN | |
| g68 | detail 'CORNER BOND BEAM DETAIL' removed (18 text items) added 2x BLOCKING EA added SIDE OF HEADER added TO ADJACENT STUD added (2) 2x6 JACK STUDS removed removed removed removed removed removed removed removed removed removed removed removed removed removed | |
| g69 | detail 1 'STRUCTURAL SECTION 1' added (2) 2x6 JACK STUDS added AND (2)2x6 KING added STUDS | |
| g70 | detail 1 'STRUCTURAL SECTION 1' added 2x6 @16" O.C. added BEARING WALL | |
| g71 | detail 1 'STRUCTURAL SECTION 1' | |
| g72 | removed | |
| g73 | removed | |
| g74 | 'TYPICAL INTERIOR SLAB DETAIL' removed removed | |
| g75 | 'TYPICAL INTERIOR SLAB DETAIL' removed removed | |
| g76 | detail 'HORIZ JOINT REINFORCEMENT' removed (3 text items) removed removed removed | |
| g77 | 'TYPICAL INTERIOR SLAB DETAIL' removed removed | |
| g78 | detail 1 'STRUCTURAL SECTION 1' graphic: linework drawn differently (no text); 129 px added, 4105 px removed at 1.5 px/pt: see the overlay graphic: lines of the earlier issue no longer drawn (no text); 0 px added, 721 px removed at 1.5 px/pt: see the overlay graphic: lines of the earlier issue no longer drawn (no text); 0 px added, 454 px removed at 1.5 px/pt: see the overlay graphic: lines of the earlier issue no longer drawn (no text); 0 px added, 453 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 113 px added, 111 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 164 px added, 191 px removed at 1.5 px/pt: see the overlay graphic: lines of the earlier issue no longer drawn (no text); 0 px added, 89 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 118 px added, 107 px removed at 1.5 px/pt: see the overlay | LOW: check |
| g79 | graphic: linework drawn differently (no text); 37118 px added, 55815 px removed at 1.5 px/pt: see the overlay | LOW: check |
| Sheet S301 39 changes | ||
| g80 | detail 1 'STRUCTURAL SECTION 2' added SPLICE IN (N) CUT added CMU BLOCKS AS added WALL added REQUIRED TO added FINISH OPENING IN added EXISTING CMU | |
| g81 | detail 1 'STRUCTURAL SECTION 2' added S301 | |
| g82 | detail 1 'STRUCTURAL SECTION 2' added S301 removed removed removed | |
| g83 | detail 2 '(N) CMU WALL TO (E) FOUNDATION' added FIRST FLOOR added 0' -0" graphic: linework drawn differently (no text); 290 px added, 77 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 3645 px added, 7529 px removed at 1.5 px/pt: see the overlay | |
| g84 | note (2 text items, 1 graphic area) added FIRST FLOOR added 0' -0" graphic: lines drawn in the new issue only (no text); 378 px added, 0 px removed at 1.5 px/pt: see the overlay | |
| g85 | new detail 3 '(N) CMU WALL TO (E) FOUNDATION1' (11 text items, 3 graphic areas) added S301 SCALE: 3/4" = 1'-0" added PSL POST added SEEPLAN added FURRING AS REQUIRED TO added FLUSH OUT PSL POST added WITH 2x8 STUD FRAMING added BEYOND added SIMPSONABA66Z w/ added 5/8"Øx6" TITEN HD ANCHOR added TO (E) FOUNDATION added (N) CMU WALL TO (E) FOUNDATION1 graphic: linework drawn differently (no text); 6057 px added, 291 px removed at 1.5 px/pt: see the overlay graphic: lines drawn in the new issue only (no text); 649 px added, 0 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 71 px added, 28 px removed at 1.5 px/pt: see the overlay | |
| g86 | detail 1 'STRUCTURAL SECTION 2' added (N) W8x31 | |
| g87 | detail 1 'STRUCTURAL SECTION 2' removed | |
| g88 | detail 1 'STRUCTURAL SECTION 2' added PSL POST added SEE PLAN | |
| g89 | detail 1 'STRUCTURAL SECTION 2' removed removed | |
| g90 | detail 1 'STRUCTURAL SECTION 2' added PSL POST added SEE PLAN | |
| g91 | new detail 4 'STEEL BEAM TO PSL POST CONNECTION' (14 text items, 3 graphic areas) added SEE PLAN added (N) W-SECTION added BEAM added PL3/8"x4x0'-8" w/ added (2) 1/2"Ø A307 added THRU BOLTS IN added 9/16"Ø HOLES added EQEQ added 2" added 2" added 5 3/8" added 4" added STEEL BEAM TO PSL POST CONNECTION added S301 SCALE: 1" = 1'-0" graphic: lines drawn in the new issue only (no text); 5689 px added, 0 px removed at 1.5 px/pt: see the overlay graphic: lines drawn in the new issue only (no text); 889 px added, 0 px removed at 1.5 px/pt: see the overlay graphic: lines drawn in the new issue only (no text); 68 px added, 0 px removed at 1.5 px/pt: see the overlay | |
| g92 | note (3 text items) added SEE PLAN added (N) W-SECTION added BEAM | |
| g93 | new detail 'NAILER TO STEEL BEAM CONNECTION' (15 text items, 1 graphic area) added SEE PLAN added (2) 2x10 NAILER added PL3/8"x4x0'-8" w/ added (2) 1/2"Ø A307 added 1/4" LAG SCREWS @12" O.C. added THRU BOLTS IN added 1/4" GAP MAX BETWEEN added STAGGER EA SIDE OF BEAM added 9/16"Ø HOLES added TOP OF PSL POST AND added BTM OF STEEL BEAM added PRIOR TO ADDING SHIMS added NAILER TO STEEL BEAM CONNECTION added SCALE: 1" = 1'-0" added (N) PSL POST graphic: lines drawn in the new issue only (no text); 2811 px added, 0 px removed at 1.5 px/pt: see the overlay | |
| g94 | detail 1 'STRUCTURAL SECTION 2' added 2x8 @16" O.C. WALL | |
| g95 | detail 2 '(N) CMU WALL TO (E) FOUNDATION' added 2x8 FRAMING PER added SECTION | |
| g96 | detail 2 '(N) CMU WALL TO (E) FOUNDATION' added ½"x5" TAPCON+ SCREW added ANCHOR W/ SIMPSON added BPS1/2-3 AND STANDARD added 1/2"Ø CUT WASHER, TYPICAL | |
| g97 | detail 2 '(N) CMU WALL TO (E) FOUNDATION' added PT2x8 SILL PLATE | |
| g98 | note (3 text items) added STEEL SHIMS AS added REQUIRED FOR added TIGHT FIT | |
| g99 | added 1/4" MAX graphic: lines drawn in the new issue only (no text); 5217 px added, 0 px removed at 1.5 px/pt: see the overlay | |
| g100 | added 8" | |
| g101 | added 1 1/2" | |
| g102 | added 3" | |
| g103 | added 3 1/2" | |
| g104 | detail 1 'STRUCTURAL SECTION 2' removed | |
| g105 | detail 1 'STRUCTURAL SECTION 2' removed removed removed graphic: lines drawn in the new issue only (no text); 306 px added, 0 px removed at 1.5 px/pt: see the overlay | |
| g106 | detail 1 'STRUCTURAL SECTION 2' removed removed | |
| g107 | detail 1 'STRUCTURAL SECTION 2' removed removed | |
| g108 | detail 1 'STRUCTURAL SECTION 2' removed | |
| g109 | detail 1 'STRUCTURAL SECTION 2' removed removed removed removed removed graphic: lines drawn in the new issue only (no text); 168 px added, 0 px removed at 1.5 px/pt: see the overlay | |
| g110 | detail 1 'STRUCTURAL SECTION 2' removed | |
| g111 | note (2 text items) removed removed | |
| g112 | note (6 text items) removed removed removed removed removed removed | |
| g113 | detail 3 '(N) CMU WALL TO (E) FOUNDATION1' removed removed | |
| g114 | detail 2 '(N) CMU WALL TO (E) FOUNDATION' removed graphic: lines drawn in the new issue only (no text); 233 px added, 0 px removed at 1.5 px/pt: see the overlay | |
| g115 | graphic: linework drawn differently (no text); 47800 px added, 41470 px removed at 1.5 px/pt: see the overlay | LOW: check |
| g116 | detail 1 'STRUCTURAL SECTION 2' graphic: linework drawn differently (no text); 882 px added, 1176 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 882 px added, 588 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 1176 px added, 1174 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 99 px added, 9 px removed at 1.5 px/pt: see the overlay | LOW: check |
| g117 | detail 2 '(N) CMU WALL TO (E) FOUNDATION' graphic: lines of the earlier issue no longer drawn (no text); 0 px added, 316 px removed at 1.5 px/pt: see the overlay | LOW: check |
| g118 | graphic: lines drawn in the new issue only (no text); 72 px added, 0 px removed at 1.5 px/pt: see the overlay | LOW: check |
| Sheet S302 18 changes | ||
| g119 | ||
| g120 | note (6 text items) removed removed removed | |
| g121 | note (6 text items) added ½"x5" TAPCON+ SCREW added ANCHOR W/ SIMPSON added BPS1/2-3 AND STANDARD added 1/2"Ø CUT WASHER, TYPICAL removed removed | |
| g122 | note (2 text items) added CONCRETE SIDEWALK added SEE CIVIL | |
| g123 | note (2 text items) added #5 @ 16" O.C. added EACH WAY | |
| g124 | note (2 text items) added #5 DOWELS added @ 16" O.C. | |
| g125 | added 3 -#5x CONTINUOUS | |
| g126 | graphic: linework drawn differently (no text); 5 px added, 73 px removed at 1.5 px/pt: see the overlay graphic: lines of the earlier issue no longer drawn (no text); 0 px added, 69 px removed at 1.5 px/pt: see the overlay | |
| g127 | added 3 1/8" | |
| g128 | added 3 1/8" graphic: linework drawn differently (no text); 1087 px added, 704 px removed at 1.5 px/pt: see the overlay | |
| g129 | added 1 1/2" | |
| g130 | added 1 1/2" | |
| g131 | added 1/4" / 1'-0" | |
| g132 | removed | |
| g133 | note (5 text items) removed removed removed removed removed | |
| g134 | note (3 text items) removed removed removed | |
| g135 | graphic: linework drawn differently (no text); 32578 px added, 34871 px removed at 1.5 px/pt: see the overlay | LOW: check |
| g136 | graphic: linework drawn differently (no text); 752 px added, 418 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 819 px added, 838 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 401 px added, 380 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 833 px added, 1037 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 56 px added, 59 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 530 px added, 545 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 819 px added, 768 px removed at 1.5 px/pt: see the overlay | LOW: check |
| Sheet S303 21 changes | ||
| g137 | detail 1 'STRUCTURAL SECTION 4' added TRUSS BRIDGING added PER TRUSS MANF. | |
| g138 | detail 1 'STRUCTURAL SECTION 4' added (N) W8x31 | |
| g139 | detail 1 'STRUCTURAL SECTION 4' added WOOD HEADER added SEE PLAN | |
| g140 | detail 1 'STRUCTURAL SECTION 4' added @16" O.C. removed graphic: linework drawn differently (no text); 250 px added, 192 px removed at 1.5 px/pt: see the overlay | |
| g141 | detail 1 'STRUCTURAL SECTION 4' added @ 16" O.C. added #5 DOWELS | |
| g142 | detail 1 'STRUCTURAL SECTION 4' added CONCRETE SIDEWALK added FROST PROTECTED added SEE CIVIL added SEE CIVIL added ENTRY PAD | |
| g143 | detail 1 'STRUCTURAL SECTION 4' added 2'-0" #4 BARS @16" O.C. added GROUTED INTO added BUILDING SLAB 6" MIN | |
| g144 | detail 1 'STRUCTURAL SECTION 4' added 2'-0" #4 BARS @16" O.C. added GROUTED INTO added FOUNDATION WALL added 6" MIN | |
| g145 | detail 1 'STRUCTURAL SECTION 4' added 24" | |
| g146 | detail 1 'STRUCTURAL SECTION 4' added 24" added #4 DOWELS @ 16" | |
| g147 | detail 1 'STRUCTURAL SECTION 4' added 24" | |
| g148 | detail 1 'STRUCTURAL SECTION 4' added 24" added #4 DOWELS @ 16" | |
| g149 | detail 1 'STRUCTURAL SECTION 4' removed removed | |
| g150 | detail 1 'STRUCTURAL SECTION 4' added #5 @ 16" O.C. added EACH WAY | |
| g151 | detail 1 'STRUCTURAL SECTION 4' added 3 -#5x CONTINUOUS | |
| g152 | detail 1 'STRUCTURAL SECTION 4' graphic: linework drawn differently (no text); 5 px added, 72 px removed at 1.5 px/pt: see the overlay | |
| g153 | detail 1 'STRUCTURAL SECTION 4' removed removed | |
| g154 | detail 1 'STRUCTURAL SECTION 4' removed removed removed removed removed | |
| g155 | detail 1 'STRUCTURAL SECTION 4' removed removed | |
| g156 | graphic: linework drawn differently (no text); 59325 px added, 26220 px removed at 1.5 px/pt: see the overlay | LOW: check |
| g157 | detail 1 'STRUCTURAL SECTION 4' graphic: linework drawn differently (no text); 62 px added, 79 px removed at 1.5 px/pt: see the overlay graphic: linework drawn differently (no text); 63 px added, 80 px removed at 1.5 px/pt: see the overlay | LOW: check |
In the narrative and found (8)
| Change | Old to new | |
|---|---|---|
| Sheet S001 3 changes | ||
| g8 | ||
| g16 | note (9 text items, 1 graphic area) added WOOD STRUCTURAL PANEL NOTES: added STRUCTURAL WOOD PANELS SHALL CONFORM TO THE REQUIREMENTS OF ONE OF THE added FOLLOWING STANDARD: added U.S. PRODUCT STANDARD PS1-95 FOR CONSTRUCTION AND INDUSTRIAL PLYWOOD. added U.S. PRODUCT STANDARD PS2-92 PERFORMANCE STANDARD FOR WOOD BASED added STRUCTURAL USE PANELS added APA PRP-108 PERFORMANCE STANDARDS added ANY CODE-APPROVED STANDARD OR PUBLICATION. APPROVAL MUST BE OBTAINED added FROM STRUCTURAL ENGINEERS. graphic: lines drawn in the new issue only (no text); 163 px added, 0 px removed at 1.5 px/pt: see the overlay | |
| g36 | removed | |
| Sheet S101 2 changes | ||
| g43 | new detail 2 'SLAB AND FRAMING PLAN' (35 text items) added S301 added 2x6 @16" O.C. added 2x6 @16" O.C. added 2x6 @16" O.C. added 2x6 @16" O.C. added BEARING WALL added BEARING WALL added BEARING WALL added (N) 2x8 @16" O.C. added INFILL WALL SEE added SECTIONS FOR added MORE INFO added 5¼"x5¼" PSL added 5¼"x5¼" PSL added POST UP added POST UP added POST UP added S300 added 5" SLAB w/ added #4 @16" O.C. added OVER 10 MIL VAPOR BARRIER added AND MIN 6" STRUCTURAL BACK FILL added w/ ZIP R-6 added SHEATHING added HSS4X4X5/16 added FROST PROTECTED added CONCRETE SIDEWALK added CONCRETE SIDEWALK added ENTRY PAD added SEE CIVIL added SEE CIVIL added SEE CIVIL added S200 added SLAB AND FRAMING PLAN | |
| g48 | detail 2 'SLAB AND FRAMING PLAN' removed | |
| Sheet S200 3 changes | ||
| g62 | detail 1 'STRUCTURAL FRONT ELEVATION' removed | |
| g63 | detail 1 'STRUCTURAL FRONT ELEVATION' removed | |
| g64 | graphic: linework drawn differently (no text); 25423 px added, 3077 px removed at 1.5 px/pt: see the overlay | |